ICSA-21-159-03 | AVEVA InTouch | The vulnerability could expose cleartext credentials from InTouch Runtime (WindowViewer) if an authorized, privileged user creates a diagnostic memory dump of the process and saves it to a non-protected location.CVE-2021-32942 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:N). | [] | null | null | 6.6 | null |
ICSA-21-355-04 | Emerson DeltaV | A specially crafted script could cause a controller to restart and cause a denial-of-service condition.CVE-2021-26264 has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:C/C:N/I:N/A:H). Missing DLLs, if replaced by an insider, could allow an attacker to achieve local privilege escalation when some DeltaV services are started.CVE-2021-44463 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:R/S:C/C:L/I:H/A:H). | [] | null | null | 8.1 | null |
ICSA-22-349-11 | Siemens SIPROTEC 5 Devices | A buffer overrun can be triggered in X.509 certificate verification, specifically in name constraint checking. Note that this occurs after certificate chain signature verification and requires either a CA to have signed the malicious certificate or for the application to continue certificate verification despite failure to construct a path to a trusted issuer. An attacker can craft a malicious email address to overflow four attacker-controlled bytes on the stack. This buffer overflow could result in a crash (causing a denial of service) or potentially remote code execution. Many platforms implement stack overflow protections which would mitigate against the risk of remote code execution. The risk may be further mitigated based on stack layout for any given platform/compiler. Pre-announcements of CVE-2022-3602 described this issue as CRITICAL. Further analysis based on some of the mitigating factors described above have led this to be downgraded to HIGH. Users are still encouraged to upgrade to a new version as soon as possible. In a TLS client, this can be triggered by connecting to a malicious server. In a TLS server, this can be triggered if the server requests client authentication and a malicious client connects. Fixed in OpenSSL 3.0.7 (Affected 3.0.0,3.0.1,3.0.2,3.0.3,3.0.4,3.0.5,3.0.6). A buffer overrun can be triggered in X.509 certificate verification, specifically in name constraint checking. Note that this occurs after certificate chain signature verification and requires either a CA to have signed a malicious certificate or for an application to continue certificate verification despite failure to construct a path to a trusted issuer. An attacker can craft a malicious email address in a certificate to overflow an arbitrary number of bytes containing the `.' character (decimal 46) on the stack. This buffer overflow could result in a crash (causing a denial of service). In a TLS client, this can be triggered by connecting to a malicious server. In a TLS server, this can be triggered if the server requests client authentication and a malicious client connects. Fixed in OpenSSL 3.0.7 (Affected 3.0.0,3.0.1,3.0.2,3.0.3,3.0.4,3.0.5,3.0.6). | [] | null | 7.5 | null | null |
ICSMA-17-215-01 | ICSMA-17-215-01_Siemens Molecular Imaging Vulnerabilities | An unauthenticated remote attacker could execute arbitrary code via a specially crafted remote procedure call (RPC) request sent to the server service of affected Microsoft Windows systems. An unauthenticated remote attacker could execute arbitrary code with the permissions of the web server by sending a specially crafted HTTP request to the WebDAV service. | [] | null | null | 9.8 | null |
ICSA-20-303-01 | Mitsubishi Electric MELSEC iQ-R, Q, and L Series (Update D) | Mitsubishi Electric MELSEC iQ-R, Q, and L Series CPU modules are vulnerable to uncontrolled resource consumption. When the CPU module receives a specially crafted packet from a malicious attacker, Ethernet communication may enter a denial-of-service condition and a reset is required to recover it. | [] | null | 7.5 | null | null |
ICSA-19-246-01 | EZAutomation EZ Touch Editor | An attacker could use a specially crafted project file to overflow the buffer and execute code under the privileges of the application.CVE-2019-13518 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). | [] | null | null | 7.8 | null |
ICSA-21-103-02 | Advantech WebAccessSCADA | Incorrect permissions are set to default on the -Project Management ' page of WebAccess/SCADA portal, which may allow a low-privileged user to update an administrator 's password and login as an administrator to escalate privileges on the system.CVE-2021-22669 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H). | [] | null | null | 8.8 | null |
ICSA-22-342-01 | Advantech iView | Advantech iView versions 5.7.04.6469 and prior are vulnerable to a SQL injection that could disclose sensitive product information to an unauthorized user.CVE-2022-3323 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). | [] | null | null | 7.5 | null |
ICSA-24-011-08 | Siemens SICAM A8000 | The network configuration service of affected devices contains a flaw in the conversion of ipv4 addresses that could lead to an uninitialized variable being used in succeeding validation steps.
By uploading specially crafted network configuration, an authenticated remote attacker could be able to inject commands that are executed on the device with root privileges during device startup. | [] | null | 6.6 | null | null |
ICSA-20-105-09 | Siemens TIM 3V-IE and 4R-IE Family Devices | The affected versions contain an open debug port that is available under certain specific conditions. The vulnerability is only available if the IP address is configured to 192.168.1.2. If available, the debug port could be exploited by an attacker with network access to the device. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known. | [] | null | 9 | null | null |
ICSA-20-142-01 | Johnson Controls Software House C-CURE 9000 and American Dynamics victor VMS | During installation or upgrade to C•CURE 9000 v2.70 and victor Video Management System v5.2, the credentials of the user performing the installation or upgrade are saved in a file. The install log file persists after the installation.CVE-2020-9045 has been assigned to this vulnerability. A CVSS v3 base score of 9.9 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H). | [] | null | null | 9.9 | null |
ICSA-18-114-02 | Intel 2G Modem | Buffer overflow in ETWS processing module allows a remote attacker to potentially execute arbitrary code via an adjacent network.CVE-2018-3624 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:L). | [] | null | null | 8.2 | null |
ICSA-18-025-01 | Nari PCS-9611 (Update A) | An improper input validation vulnerability has been identified that affects a service within the software that may allow a remote attacker to arbitrarily read/access system resources and affect the availability of the system. CVE-2018-5447 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). | [] | null | null | 9.8 | null |
ICSA-19-192-02 | Siemens SIMATIC WinCC and PCS7 (Update C) | The SIMATIC WinCC DataMonitor web application of the affected products allows to upload arbitrary ASPX code. The security vulnerability could be exploited by an authenticated attacker with network access to the WinCC DataMonitor application. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known. | [] | null | null | 7.2 | null |
ICSA-22-286-08 | Siemens TCP Event Service of SCALANCE And RUGGEDCOM Devices | Affected devices with TCP Event service enabled do not properly handle malformed packets.
This could allow an unauthenticated remote attacker to cause a denial of service condition and reboot the device thus possibly affecting other network resources. | [] | null | 8.6 | null | null |
ICSA-19-213-02 | Fuji Electric FRENIC Loader | The affected product is vulnerable to an out-of-bounds read vulnerability, which may allow an attacker to read limited information from the device.CVE-2019-13512 has been assigned to this vulnerability. A CVSS v3 base score of 4.4 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:L). | [] | null | null | 4.4 | null |
ICSA-19-029-02 | Mitsubishi Electric MELSEC-Q Series PLCs | A remote attacker can send specific packets over several ports on the affected products that will result in an Ethernet communication crash. | [] | null | null | 7.5 | null |
ICSA-20-042-09 | Siemens OZW Web Server | Vulnerable versions of OZW Web Server use predictable path names for project files that legitimately authenticated users have created by using the application's export function. By accessing a specific uniform resource locator on the web server, a remote attacker could be able to download a project file without prior authentication. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected system. No user interaction is required to exploit this security vulnerability. Successful exploitation of the security vulnerability compromises the confidentiality of the targeted system. | [] | null | 5.3 | null | null |
ICSA-22-286-12 | Siemens APOGEE, TALON and Desigo PXC/PXM Products | The FTP server does not properly release memory resources that were reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the FTP server. | [] | null | 7.5 | null | null |
ICSA-18-011-01 | WECON Technology Co., Ltd. LeviStudio HMI Editor | Specially-crafted malicious files may be able to cause stack-based buffer overflow vulnerabilities, which may allow remote code execution. CVE-2017-16739 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L). A specially-crafted malicious file may be able to cause a heap-based buffer overflow vulnerability when opened by a user. CVE-2017-16737 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L). | [] | null | null | 5.3 | null |
ICSA-23-271-01 | Rockwell Automation PanelView 800 | An input/output validation vulnerability exists in a third-party component that the PanelView 800 utilizes. Libpng, which is PNG's reference library, version 1.6.32 and earlier does not properly check the length of chunks against the user limit. Libpng versions prior to 1.6.32 are susceptible to a vulnerability which, when successfully exploited, could potentially lead to a disclosure of sensitive information, addition or modification of data, or a denial-of-service condition. | [] | null | null | 9.8 | null |
ICSA-17-283-01 | LAVA Computer MFG Inc. Ether-Serial Link | An improper authentication vulnerability has been identified, which, if exploited, would allow an attacker with the same IP address to bypass authentication by accessing a specific uniform resource locator.CVE-2017-14003 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H). | [] | null | null | 8.1 | null |
ICSA-18-060-01 | ICSA-18-060-01_Siemens SIMATIC, SIMOTION, and SINUMERIK (Update A) | Multiple buffer overflows could allow attackers to execute arbitrary code. Local access to the system is required to exploit this vulnerability. CVE-2017-5705, CVE-2017-5706, and CVE-2017-5707 have been assigned to these vulnerabilities. A CVSS v3 base score of 8.2 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H). A buffer overflow could allow remote authenticated attackers to execute arbitrary code with extended privileges.CVE-2017-5712 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H). Multiple privilege escalations could allow unauthenticated access to sensitive data.CVE-2017-5708, CVE-2017-5709, and CVE-2017-5710 have been assigned to these vulnerabilities. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:N). | [] | null | null | 8.2 | null |
ICSA-23-285-02 | Siemens SCALANCE W1750D | There are buffer overflow vulnerabilities in multiple underlying services that could lead to unauthenticated remote code execution by sending specially crafted packets destined to the PAPI (Aruba's access point management protocol) UDP port (8211). Successful exploitation of these vulnerabilities result in the ability to execute arbitrary code as a privileged user on the underlying operating system. There are buffer overflow vulnerabilities in multiple underlying services that could lead to unauthenticated remote code execution by sending specially crafted packets destined to the PAPI (Aruba's access point management protocol) UDP port (8211). Successful exploitation of these vulnerabilities result in the ability to execute arbitrary code as a privileged user on the underlying operating system. There are buffer overflow vulnerabilities in multiple underlying services that could lead to unauthenticated remote code execution by sending specially crafted packets destined to the PAPI (Aruba's access point management protocol) UDP port (8211). Successful exploitation of these vulnerabilities result in the ability to execute arbitrary code as a privileged user on the underlying operating system. There are buffer overflow vulnerabilities in multiple underlying services that could lead to unauthenticated remote code execution by sending specially crafted packets destined to the PAPI (Aruba's access point management protocol) UDP port (8211). Successful exploitation of these vulnerabilities result in the ability to execute arbitrary code as a privileged user on the underlying operating system. There are buffer overflow vulnerabilities in multiple underlying services that could lead to unauthenticated remote code execution by sending specially crafted packets destined to the PAPI (Aruba's access point management protocol) UDP port (8211). Successful exploitation of these vulnerabilities result in the ability to execute arbitrary code as a privileged user on the underlying operating system. There are buffer overflow vulnerabilities in multiple underlying services that could lead to unauthenticated remote code execution by sending specially crafted packets destined to the PAPI (Aruba's access point management protocol) UDP port (8211). Successful exploitation of these vulnerabilities result in the ability to execute arbitrary code as a privileged user on the underlying operating system. There are buffer overflow vulnerabilities in multiple underlying services that could lead to unauthenticated remote code execution by sending specially crafted packets destined to the PAPI (Aruba's access point management protocol) UDP port (8211). Successful exploitation of these vulnerabilities result in the ability to execute arbitrary code as a privileged user on the underlying operating system. There are buffer overflow vulnerabilities in multiple underlying services that could lead to unauthenticated remote code execution by sending specially crafted packets destined to the PAPI (Aruba's access point management protocol) UDP port (8211). Successful exploitation of these vulnerabilities result in the ability to execute arbitrary code as a privileged user on the underlying operating system. An unauthenticated Denial of Service (DoS) vulnerability exists in a service accessed via the PAPI protocol provided by Aruba InstantOS and ArubaOS 10. Successful exploitation of this vulnerability results in the ability to interrupt the normal operation of the affected access point. Multiple authenticated command injection vulnerabilities exist in the Aruba InstantOS and ArubaOS 10 command line interface. Successful exploitation of these vulnerabilities result in the ability to execute arbitrary commands as a privileged user on the underlying operating system. Multiple authenticated command injection vulnerabilities exist in the Aruba InstantOS and ArubaOS 10 command line interface. Successful exploitation of these vulnerabilities result in the ability to execute arbitrary commands as a privileged user on the underlying operating system. Multiple authenticated command injection vulnerabilities exist in the Aruba InstantOS and ArubaOS 10 command line interface. Successful exploitation of these vulnerabilities result in the ability to execute arbitrary commands as a privileged user on the underlying operating system. A vulnerability exists in Aruba InstantOS and ArubaOS 10 where an edge-case combination of network configuration, a specific WLAN environment and an attacker already possessing valid user credentials on that WLAN can lead to sensitive information being disclosed via the WLAN. The scenarios in which this disclosure of potentially sensitive information can occur are complex and depend on factors that are beyond the control of the attacker. | [] | null | 5.4 | null | null |
ICSA-21-334-04 | Johnson Controls CEM Systems AC2000 | The affected product has an off-by-one error vulnerability, which may allow an attacker to achieve super user access on the operating system.CVE-2021-3156 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H). | [] | null | null | 7.8 | null |
ICSA-22-228-07 | Sequi PortBloque S | The affected product has improper authentication issues which may allow an attacker to bypass the authentication process and gain user-level access to the device.CVE-2022-2662 has been assigned to this vulnerability. A CVSS v3 base score of 9.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H). The affected product has an improper authorization vulnerability, which may allow a low-privileged user to perform administrative functions using specifically crafted requests.CVE-2022-2661 has been assigned to this vulnerability. A CVSS v3 base score of 9.9 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H). | [] | null | null | 9.9 | null |
ICSA-21-278-03 | Moxa MXview Network Management Software | A path traversal vulnerability in the application may allow an attacker to create or overwrite critical files used to execute code, such as programs or libraries.CVE-2021-38452 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N). The affected product uses hard-coded passwords, which may allow an attacker to gain access through accounts using default passwords.CVE-2021-38456 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). The affected product is vulnerable to password leakage, which may allow an attacker to obtain credentials through unprotected transport.CVE-2021-38460 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). The affected product is vulnerable to improper neutralization of special elements, which may allow an attacker to remotely execute unauthorized commands. This could allow an attacker to disable software or read and modify otherwise inaccessible data.CVE-2021-38458 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). The affected product has a misconfigured service that allows remote connections to internal communication channels, which may allow an attacker to interact and use MQTT remotely.CVE-2021-38454 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:N). | [] | null | null | 10 | null |
ICSA-23-271-01 | Rockwell Automation PanelView 800 | An input/output validation vulnerability exists in a third-party component that the PanelView 800 utilizes. Libpng, which is PNG's reference library, version 1.6.32 and earlier does not properly check the length of chunks against the user limit. Libpng versions prior to 1.6.32 are susceptible to a vulnerability which, when successfully exploited, could potentially lead to a disclosure of sensitive information, addition or modification of data, or a denial-of-service condition. | [] | null | null | 9.8 | null |
ICSA-21-035-02 | Horner Automation Cscape | The affected application lacks proper validation of user-supplied data when parsing project files. This could lead to an out-of-bounds read. An attacker could leverage this vulnerability to execute code in the context of the current process.CVE-2021-22663 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). | [] | null | null | 7.8 | null |
ICSA-23-136-01 | Snap One OvrC Cloud | In Snap One OVRC cloud platform, the Hub is a device that is used to centralize and manage nested devices connected to it. A vulnerability exists where an attacker can impersonate a hub and send device requests to claim already claimed devices. The OVRC cloud platform receives the requests but does not validate if the found devices are already managed by another user. CVE-2023-28649 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H). When supplying Snap One OVRC cloud servers with a random MAC address, it will return information about the device. The MAC address of devices can be enumerated in an attack and their information will be disclosed by the OVRC cloud. CVE-2023-28412 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). Snap One OVRC cloud servers contain a route that can be exploited where an attacker can use to bypass requirements and claim devices outright. CVE-2023-31241 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H). Snap One OvrC Pro versions prior to 7.3 utilize HTTP connections when downloading a program from their servers. Because it does not use HTTPS, OVRC Pro devices are susceptible to exploitation. CVE-2023-31193 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). Snap One OVRC Pro devices versions 7.2 and prior do not validate firmware updates correctly. The device only calculates the MD5 hash of the firmware and does not check using a private-public key mechanism. The lack of complete PKI system and lack of firmware signature could allow attackers to upload arbitrary firmware updates resulting in code execution. CVE-2023-28386 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:N). Devices using Snap One OVRC cloud are sent to web address when accessing a web management interface utilizing a HTTP connection. It is possible for attackers to impersonate a device and supply malicious information about the device’s web server interface. By supplying malicious parameters, an attacker could redirect the user to arbitrary and dangerous locations on the web. CVE-2023-31245 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L). Snap One OvrC Pro versions prior to 7.2 have their own locally running web server accessible both from the local network and remotely. OvrC cloud contains a hidden superuser account that is accessible through hard-coded credentials. CVE-2023-31240 has been assigned to this vulnerability. A CVSS v3 base score of 8.3 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:L/A:L). In Snap One OvrC Pro versions prior to 7.2, when logged into the superuser account, a new functionality appears that allows a user to execute arbitrary commands on the hub device. CVE-2023-25183 has been assigned to this vulnerability. A CVSS v3 base score of 8.3 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:L/A:L). | [] | null | null | 8.3 | null |
ICSA-23-355-01 | FXC AE1021/AE1021PE | FXC AE1021/AE1021PE versions 2.0.9 and prior are vulnerable to a code injection that could allow an authenticated user to achieve remote code execution via NTP server settings. | [] | null | 8 | null | null |
ICSA-19-248-01 | Red Lion Controls Crimson | Multiple vulnerabilities can be exploited when a valid user opens a specially crafted, malicious input file that can reference memory after it has been freed.CVE-2019-10996 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). Multiple vulnerabilities can be exploited when a valid user opens a specially crafted, malicious input file that operates outside of the designated memory area.CVE-2019-10978 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:N). Multiple vulnerabilities can be exploited when a valid user opens a specially crafted, malicious input file that causes the program to mishandle pointers.CVE-2019-10984 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). Crimson uses a hard-coded password to encrypt protected files in transit and at rest, which may allow an attacker to access configuration files.CVE-2019-10990 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N). | [] | null | null | 6.5 | null |
ICSA-22-167-10 | Siemens SCALANCE XM-400 and XR-500 | The OSPF protocol implementation in affected devices fails to verify the checksum and length fields in the OSPF LS Update messages.
An unauthenticated remote attacker could exploit this vulnerability to cause interruptions in the network by sending specially crafted OSPF packets. Successful exploitation requires OSPF to be enabled on an affected device. | [] | null | 5.9 | null | null |
ICSA-18-290-01 | Omron CX-Supervisor (Update A) | When processing project files and tampering with a specific byte, memory corruption may occur within a specific object.CVE-2018-17905 has been assigned to this vulnerability. A CVSS v3 base score of 4.5 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:N/UI:R/S:U/C:L/I:L/A:L). When processing project files and tampering with the value of an offset, an attacker can force the application to read a value outside of an array.CVE-2018-17907 has been assigned to this vulnerability. A CVSS v3 base score of 2.5 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:N/UI:R/S:U/C:L/I:N/A:N). When processing project files the application fails to check if it is referencing freed memory, which may allow an attacker to execute code in under the context of the application.CVE-2018-17909 has been assigned to this vulnerability. A CVSS v3 base score of 4.5 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:N/UI:R/S:U/C:L/I:L/A:L). A type confusion vulnerability exists when processing project files, which may allow an attacker to execute code in the context of the application.CVE-2018-17913 has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H). | [] | null | null | 7 | null |
ICSA-18-296-01 | Advantech WebAccess | Several stack-based buffer overflow vulnerabilities have been identified, which may allow an attacker to execute arbitrary code.CVE-2018-14816 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). A .dll component is susceptible to external control of file name or path vulnerability, which may allow an arbitrary file deletion when processing.CVE-2018-14820 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). An improper privilege management vulnerability has been identified, which may allow an attacker to access those files and perform actions at a system administrator level.CVE-2018-14828 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H). A path traversal vulnerability may allow an attacker to execute arbitrary code.CVE-2018-14806 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). | [] | null | null | 9.8 | null |
ICSA-20-035-01 | ICSA-20-035-01_AutomationDirect C-More Touch Panels | It is possible to unmask credentials and other sensitive information on unprotected project files, which may allow an attacker to remotely access the system and manipulate system configurations.CVE-2020-6969 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H). | [] | null | null | 10 | null |
ICSA-23-017-01 | GE Digital Proficy Historian | Even if the authentication fails for local service authentication, the requested command could still execute regardless of authentication status.-CVE-2022-46732 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). An unauthorized user could alter or write files with full control over the path and content of the file.-CVE-2022-46660 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N). An unauthorized user could be able to read any file on the system, potentially exposing sensitive information.-CVE-2022-43494 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). An unauthorized user could possibly delete any file on the system.-CVE-2022-46331 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N). An unauthorized user with network access and the decryption key could decrypt sensitive data, such as usernames and passwords.-CVE-2022-38469 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). | [] | null | null | 7.5 | null |
ICSA-18-317-07 | Siemens SIMATIC IT Production Suite | An attacker with network access to the installation could bypass the application-level authentication. In order to exploit the vulnerability, an attacker must obtain network access to an affected installation and must obtain a valid username to the system. Successful exploitation requires no user privileges and no user interaction. The vulnerability could allow an attacker to compromise confidentiality, integrity and availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known. | [] | null | null | 7.7 | null |
ICSA-22-109-04 | Elcomplus SmartPTT SCADA | An attacker can inject JavaScript code into a specific parameter that can executed upon accessing the dashboard or the main page.CVE-2021-43932 has been assigned to this vulnerability. A CVSS v3 base score of 9.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:H). A low-authenticated user can access higher level administration authorization by issuing requests directly to the desired endpoints.CVE-2021-43939 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H). The backup and restore system does not adequately validate upload requests, enabling a malicious user to potentially upload arbitrary files.CVE-2021-43934 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). The backup and restore system does not adequately validate download requests, enabling malicious users to perform path traversal attacks and potentially download arbitrary files from the system.CVE-2021-43930 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N). | [] | null | null | 4.9 | null |
ICSA-21-280-06 | FATEK Automation WinProladder | A use after free vulnerability may be exploited when a valid user opens a malformed project file, which may allow arbitrary code execution.CVE-2021-38438 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). The affected product lacks proper validation of user-supplied data when parsing project files, which could result in an out-of-bounds write. An attacker could leverage this vulnerability to execute arbitrary code.CVE-2021-38426 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). The affected product lacks proper validation of user-supplied data when parsing project files, which could result in an unexpected sign extension. An attacker could leverage this vulnerability to execute arbitrary code.CVE-2021-38434 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). The affected product lacks proper validation of user-supplied data when parsing project files, which could result in a stack-based buffer overflow. An attacker could leverage this vulnerability to execute arbitrary code.CVE-2021-38430 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). The affected product lacks proper validation of user-supplied data when parsing project files, which could result in a memory-corruption condition. An attacker could leverage this vulnerability to execute arbitrary code in the context of the current process.CVE-2021-38436 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). The affected product lacks proper validation of user-supplied data when parsing project files, which could result in a heap-corruption condition. An attacker could leverage this vulnerability to execute code in the context of the current process.CVE-2021-38442 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). The affected product is vulnerable to an out-of-bounds read, which may allow an attacker to read unauthorized information.CVE-2021-38440 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:N). | [] | null | null | 3.3 | null |
ICSA-24-030-03 | Mitsubishi Electric MELSEC WS Series Ethernet Interface Module | An authentication bypass vulnerability exists in the MELSEC WS Series Ethernet Interface Modules. A remote unauthenticated attacker can bypass authentication by capture-replay attack and illegally login to the modules. As a result, the remote attacker who has logged in illegally may be able to disclose or tamper with the programs and parameters in the modules. | [] | null | 5.9 | null | null |
ICSA-23-193-01 | Rockwell Automation Select Communication Modules | Where this vulnerability exists in the 1756 EN2* and 1756 EN3* products, it could allow a malicious user to perform remote code execution with persistence on the target system through maliciously crafted CIP messages. This includes the ability to modify, deny, and exfiltrate data passing through the device. Where this vulnerability exists in the 1756-EN4* products, it could allow a malicious user to cause a denial-of-service condition by asserting the target system through maliciously crafted CIP messages. | [] | null | null | 7.5 | null |
ICSMA-21-084-01 | Philips Gemini PET/CT Family | The software stores sensitive information in a removable media device that does not have built-in access control.CVE-2021-27456 has been assigned to this vulnerability. A CVSS v3 base score of 2.4 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). | [] | null | null | 2.4 | null |
ICSA-24-079-01 | Franklin Fueling System EVO 550/5000 | Franklin Fueling System EVO 550 and EVO 5000 are vulnerable to a Path Traversal vulnerability that could allow an attacker to access sensitive files on the system. | [] | null | 7.5 | null | null |
ICSA-21-056-03 | Rockwell Automation Logix Controllers (Update A) | Studio 5000 Logix Designer uses a key to verify Logix controllers are communicating with the affected Rockwell Automation products. The product is vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Logix controllers.CVE-2021-22681 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H). | [] | null | null | 10 | null |
ICSA-20-191-02 | Rockwell Automation Logix Designer Studio 5000 | The affected product is vulnerable to an xml external entity (XXE) vulnerability, which may allow an attacker to view hostnames or other resources from the program.CVE-2020-12025 has been assigned to this vulnerability. A CVSS v3 base score of 3.6 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:C/C:L/I:N/A:N). | [] | null | null | 3.6 | null |
ICSA-20-135-01 | Opto 22 SoftPAC Project | Paths specified within the zip files used to update the SoftPAC firmware are not sanitized. As a result, an attacker with user privileges can gain arbitrary file write access with system access.CVE-2020-12042 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N). SoftPAC 's firmware files ' signatures are not verified upon firmware update. This allows an attacker to replace legitimate firmware files with malicious files.CVE-2020-12046 has been assigned to this vulnerability. A CVSS v3 base score of 5.7 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:R/S:U/C:N/I:H/A:N). SoftPACAgent communicates with SoftPACMonitor over network Port 22000. However, this port is open without any restrictions. This allows an attacker with network access to control the SoftPACAgent service including updating SoftPAC firmware, starting or stopping service, or writing to certain registry values.CVE-2020-10612 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H). SoftPAC does not specify the path of multiple imported .dll files. Therefore, an attacker can replace them and execute code whenever the service starts.CVE-2020-10616 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:N). SoftPAC communication does not include any credentials. This allows an attacker with network access to directly communicate with SoftPAC, including, for example, stopping the service remotely.CVE-2020-10620 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). | [] | null | null | 9.8 | null |
ICSA-21-336-02 | Johnson Controls Entrapass | The affected product is vulnerable to an exposure of sensitive information to an unauthorized actor.CVE-2021-36198 has been assigned to this vulnerability. A CVSS v3 base score of 8.3 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L). | [] | null | null | 8.3 | null |
ICSA-19-302-01 | PHOENIX CONTACT Automation Worx Software Suite | A manipulated PC Worx or Config+ project file could lead to arbitrary code execution due to insufficient input data validation.CVE-2019-16675 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). | [] | null | null | 7.8 | null |
ICSA-23-103-12 | Siemens Polarion ALM | The application contains a XML External Entity Injection (XXE) vulnerability. This could allow an attacker to view files on the application server filesystem. | [] | null | 5.9 | null | null |
ICSA-21-098-01 | FATEK Automation WinProladder | The affected product is vulnerable to an integer underflow, which may cause an out-of-bounds write and allow an attacker to execute arbitrary code.CVE-2021-27486has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). | [] | null | null | 7.8 | null |
ICSA-24-165-16 | Rockwell Automation FactoryTalk View SE | A user authentication vulnerability exists in FactoryTalk View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer's server to view an HMI project. This action is allowed without proper authentication verification. | [] | null | 8.6 | null | null |
ICSA-23-047-05 | Siemens SiPass integrated AC5102 / ACC-G2 and ACC-AP | Affected devices improperly sanitize user input on the telnet command line interface.
This could allow an authenticated user to escalate privileges by injecting arbitrary commands that are executed with root privileges. | [] | null | 7.8 | null | null |
ICSA-21-147-04 | Siemens JT2Go and Teamcenter Visualization | Affected applications lack proper validation of user-supplied data when parsing ASM files. This could lead to pointer dereferences of a value obtained from untrusted source. An attacker could leverage this vulnerability to execute code in the context of the current process. (ZDI-CAN-11899) Affected applications lack proper validation of user-supplied data when parsing of PAR files. This could result in a memory access past the end of an allocated buffer. An attacker could leverage this vulnerability to leak information. (ZDI-CAN-12040) Affected applications lack proper validation of user-supplied data when parsing of PAR files. This could result in a memory access past the end of an allocated buffer. An attacker could leverage this vulnerability to leak information. (ZDI-CAN-12042) Affected applications lack proper validation of user-supplied data when parsing of PAR files. This could result in a stack based buffer overflow. An attacker could leverage this vulnerability to execute code in the context of the current process. (ZDI-CAN-12041) Affected applications lack proper validation of user-supplied data when parsing of PAR files. This could result in a memory access past the end of an allocated buffer. An attacker could leverage this vulnerability to access data in the context of the current process. (ZDI-CAN-12043) | [] | null | 7.8 | null | null |
ICSA-23-103-10 | Siemens Industrial Products | The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation which leads to a restart of the webserver of the affected product. The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation of the webserver of the affected product. The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation of the webserver of the affected product. | [] | null | 7.5 | null | null |
ICSA-18-023-01 | Advantech WebAccess/SCADA | An attacker has read access to files within the directory structure of the target device. CVE-2018-5445 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). WebAccess/SCADA does not properly sanitize its inputs for SQL commands. CVE-2018-5443 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). | [] | null | null | 5.3 | null |
ICSA-23-262-01 | Siemens SIMATIC PCS neo Administration Console | The affected application leaks Windows admin credentials. An attacker with local access to the Administration Console could get the credentials, and impersonate the admin user, thereby gaining admin access to other Windows systems. | [] | null | 5.5 | null | null |
ICSA-22-349-17 | Siemens Mendix Email Connector | Affected versions of the module improperly handle access control for some module entities.
This could allow authenticated remote attackers to read and manipulate sensitive information. | [] | null | 8.1 | null | null |
ICSA-24-030-07 | Rockwell Automation LP30/40/50 and BM40 Operator Interface | After successful authentication, specifically crafted communication requests with inconsistent content can cause the CmpFiletransfer component to read internally from an invalid address, potentially leading to a denial-of-service condition. After successful authentication, specifically crafted communication requests can cause the CmpApp component to write threat actor-controlled data to memory, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpApp component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpApp component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpTraceMgr component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpTraceMgr component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpTraceMgr component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpTraceMgr component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpTraceMgr component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpTraceMgr component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpTraceMgr component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpTraceMgr component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests can cause the CmpAppForce component to write threat actor-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution. After successful authentication, specifically crafted communication requests with inconsistent content can cause the CmpApp/CmpAppBP/CmpAppForce components to read internally from an invalid address, potentially leading to a denial-of-service condition. After successful authentication, specifically crafted communication requests can cause the cmpFiletransfer component to dereference addresses provided by the request for internal read access, which can lead to a denial-of-service situation. | [] | null | 6.5 | null | null |
ICSA-22-356-03 | Mitsubishi Electric MELSEC iQ-R, iQ-L Series and MELIPC Series (Update B) | A denial-of-service vulnerability due to improper resource shutdown or release exists in Mitsubishi Electric MELSEC iQ-R, iQ-L series CPU module, and MELIPC series. This vulnerability could allow a remote attacker to cause a denial-of-service condition in the module's ethernet communication by sending specially crafted packets. | [] | null | null | 7.5 | null |
ICSMA-18-058-01 | Medtronic 2090 Carelink Programmer Vulnerabilities (Update C) | The affected product uses a per-product username and password that is stored in a recoverable format.CVE-2018-5446 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been calculated; the CVSS vector string is (AV:P/AC:H/PR:N/UI:N/S:C/C:H/I:N/A:N). The affected product 's software deployment network contains a directory traversal vulnerability that could allow an attacker to read files on the system.CVE-2018-5448 has been assigned to this vulnerability. A CVSS v3 base score of 4.8 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:L/UI:N/S:U/C:H/I:N/A:N). The affected product uses a virtual private network connection to securely download updates. The product does not verify it is still connected to this virtual private network before downloading updates. The affected products initially establish an encapsulated IP-based VPN connection to a Medtronic-hosted update network. Once the VPN is established, it makes a request to a HTTP (non-TLS) server across the VPN for updates, which responds and provides any available updates. The programmer-side (client) service responsible for this HTTP request does not check to ensure it is still connected to the VPN before making the HTTP request. Thus, an attacker could cause the VPN connection to terminate (through various methods and attack points) and intercept the HTTP request, responding with malicious updates via a man-in-the-middle attack. The affected products do not verify the origin or integrity of these updates, as it insufficiently relied on the security of the VPN. An attacker with remote network access to the programmer could influence these communications.CVE-2018-10596 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is. (AV:N/AC:H/PR:L/UI:R/S:U/C:H/I:H/A:H). | [] | null | null | 7.1 | null |
ICSA-20-051-01 | ICSA-20-051-01_B&R Automation Studio and Automation Runtime | The affected products are vulnerable to a weakness in SNMP service, which allows unauthenticated users to modify the configuration via the service.CVE-2019-19108 has been assigned to this vulnerability. A CVSS v3 base score of 9.4 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H). | [] | null | null | 9.4 | null |
ICSA-18-163-01 | Schneider Electric U.motion Builder | An input string may be evaluated as a command by the application. An attacker could exploit this to execute code, read the stack, or cause a segmentation fault in the running application.CVE-2018-7784 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H). A remote command injection allows authentication bypass.CVE-2018-7785 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H). A cross-site scripting (XSS) vulnerability exists, which could allow injection of malicious scripts.CVE-2018-7786 has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N). This vulnerability is due to improper validation of input of context parameter in HTTP GET request, which could allow the disclosure of sensitive information.CVE-2018-7787 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). | [] | null | null | 5.3 | null |
ICSA-19-183-02 | Quest KACE Systems Management Appliance | The vulnerability allows unintentional access to the appliance leveraging functions of the troubleshooting tools located in the administrator user interface. CVE-2019-10973 has been assigned to this vulnerability. A CVSS v3 base score of 2.7 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:N/A:N). | [] | null | null | 2.7 | null |
ICSA-18-044-01 | WAGO PFC200 Series | An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455. CVE-2018-5459 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). | [] | null | null | 9.8 | null |
ICSA-20-112-01 | Inductive Automation Ignition | An unprotected logging route may allow an attacker to write endless log statements into the database without space limits or authentication. This results in consuming the entire available hard-disk space, causing a denial-of-service condition.CVE-2020-10641 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H). | [] | null | null | 9.1 | null |
ICSA-21-257-09 | Siemens NX | The IFC adapter in affected application contains a use-after-free vulnerability that could be triggered while parsing user-supplied IFC files. An attacker could leverage this vulnerability to execute code in the context of the current process. The plmxmlAdapterIFC.dll contains an out-of-bounds read while parsing user supplied IFC files which could result in a read past the end of an allocated buffer. This could allow an attacker to cause a denial-of-service condition or read sensitive information from memory locations. | [] | null | 7.1 | null | null |
ICSMA-17-215-02 | ICSMA-17-215-02_Siemens Molecular Imaging Vulnerabilities | An unauthenticated remote attacker could execute arbitrary code by sending specially crafted HTTP requests to the Microsoft web server (Port 80/TCP and Port 443/TCP) of affected devices. An unauthenticated remote attacker could execute arbitrary code by sending a specially crafted request to the HP Client automation service on Port 3465/TCP of affected devices. An unauthenticated remote attacker could execute arbitrary code by sending a specially crafted request to the HP Client automation service of affected devices. An unauthenticated remote attacker could execute arbitrary code by sending a specially crafted request to the HP Client automation service of affected devices. | [] | null | null | 9.8 | null |
ICSA-21-315-02 | Multiple Data Distribution Service (DDS) Implementations (Update A) | Eclipse CycloneDDS versions prior to 0.8.0 are vulnerable to a write-what-where condition, which may allow an attacker to write arbitrary values in the XML parser.CVE-2021-38441 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H). Eclipse CycloneDDS versions prior to 0.8.0 improperly handle invalid structures, which may allow an attacker to write arbitrary values in the XML parser.CVE-2021-38443 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H). eProsima Fast DDS versions prior to 2.4.0 (#2269) are susceptible to exploitation when an attacker sends a specially crafted packet to flood a target device with unwanted traffic, which may result in a denial-of-service condition and information exposure. CVE-2021-38425 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).. --------- End Update A Part 1 of 4 ---------CVE-2021-38425 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). All versions of GurumDDS improperly calculate the size to be used when allocating the buffer, which may result in a buffer overflow.CVE-2021-38423 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H). All versions of GurumDDS are vulnerable to heap-based buffer overflow, which may cause a denial-of-service condition or remotely execute arbitrary code.CVE-2021-38439 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H). OCI OpenDDS versions prior to 3.18.1 do not handle a length parameter consistent with the actual length of the associated data, which may allow an attacker to remotely execute arbitrary code.CVE-2021-38445 has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:L/A:H). OCI OpenDDS versions prior to 3.18.1 are vulnerable when an attacker sends a specially crafted packet to flood target devices with unwanted traffic, which may result in a denial-of-service condition.CVE-2021-38447 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H). OCI OpenDDS versions prior to 3.18.1 are vulnerable when an attacker sends a specially crafted packet to flood target devices with unwanted traffic, which may result in a denial-of-service condition and information exposure. CVE-2021-38429 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).. --------- End Update A Part 2 of 4 ---------CVE-2021-38429 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). RTI Connext DDS Professional and Connext DDS Secure Versions 4.2.x to 6.1.0 are vulnerable to a stack-based buffer overflow, which may allow a local attacker to execute arbitrary code.CVE-2021-38427 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H). RTI Connext DDS Professional and Connext DDS Secure Versions 4.2x to 6.1.0 vulnerable to a stack-based buffer overflow, which may allow a local attacker to execute arbitrary code.CVE-2021-38433 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H). RTI Connext DDS Professional and Connext DDS Secure Versions 4.2x to 6.1.0 not correctly calculate the size when allocating the buffer, which may result in a buffer overflow.CVE-2021-38435 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H). RTI Connext DDS Professional, Connext DDS Secure Versions 4.2x to 6.1.0, and Connext DDS Micro Versions 2.4 and later are vulnerable when an attacker sends a specially crafted packet to flood target devices with unwanted traffic. This may result in a denial-of-service condition and information exposure. CVE-2021-38487 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).. --------- End Update A Part 3 of 4 ---------CVE-2021-38487 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). TwinOaks Computing CoreDX DDS versions prior to 5.9.1 are susceptible to exploitation when an attacker sends a specially crafted packet to flood target devices with unwanted traffic. This may result in a denial-of-service condition and information exposure. CVE-2021-43547 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).. --------- End Update A Part 4 of 4 ---------CVE-2021-43547 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). | [] | null | null | 7.5 | null |
ICSMA-20-170-05 | BIOTRONIK CardioMessenger II | The affected products do not properly enforce mutual authentication with the BIOTRONIK Remote Communication infrastructure. CVE-2019-18246 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). The affected products transmit credentials in cleartext prior to switching to an encrypted communication channel. An attacker can disclose the product 's client credentials for connecting to the BIOTRONIK Remote Communication infrastructure.CVE-2019-18248 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). The affected products allow credential reuse for multiple authentication purposes. An attacker with adjacent access to the CardioMessenger can disclose its credentials used for connecting to the BIOTRONIK Remote Communication infrastructure.CVE-2019-18252 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). The affected products do not encrypt sensitive information while at rest. An attacker with physical access to the CardioMessenger can disclose medical measurement data and the serial number from the implanted cardiac device the CardioMessenger is paired with.CVE-2019-18254 has been assigned to this vulnerability. A CVSS v3 base score of 4.6 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). The affected products use individual per-device credentials that are stored in a recoverable format. An attacker with physical access to the CardioMessenger can use these credentials for network authentication and decryption of local data in transit.CVE-2019-18256 has been assigned to this vulnerability. A CVSS v3 base score of 4.6 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). | [] | null | null | 4.6 | null |
ICSA-23-103-11 | Siemens Teamcenter Visualization and JT2Go | The APDFL.dll contains a memory corruption vulnerability while parsing specially crafted PDF files. This could allow an attacker to execute code in the context of the current process. | [] | null | 7.8 | null | null |
ICSA-23-341-02 | Schweitzer Engineering Laboratories SEL-411L | An Improper Restriction of Rendered UI Layers or Frames in the Schweitzer Engineering Laboratories SEL-411L could allow an unauthenticated attacker to perform clickjacking based attacks against an authenticated and authorized user. | [] | null | 4.3 | null | null |
ICSA-20-177-02 | Rockwell Automation FactoryTalk Services Platform XXE | A local, authenticated attacker could use an XML External Entity (XXE) attack to exploit weakly configured XML files to access local or remote content. A successful exploit could potentially cause a denial-of-service condition and allow the attacker to arbitrarily read any local file via system-level services.CVE-2020-14478 has been assigned to this vulnerability. A CVSS v3 base score of 8.4 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:H). | [] | null | null | 8.4 | null |
ICSA-18-044-01 | WAGO PFC200 Series | An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455. CVE-2018-5459 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). | [] | null | null | 9.8 | null |
ICSA-20-112-01 | Inductive Automation Ignition | An unprotected logging route may allow an attacker to write endless log statements into the database without space limits or authentication. This results in consuming the entire available hard-disk space, causing a denial-of-service condition.CVE-2020-10641 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H). | [] | null | null | 9.1 | null |
ICSA-21-005-06 | Delta Electronics CNCSoft ScreenEditor | A stack-based buffer overflow may exist when processing specially crafted project files, which may allow an attacker to execute arbitrary code.CVE-2020-27281 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). | [] | null | null | 7.8 | null |
ICSA-19-281-02 | GE Mark VIe Controller | The affected product has an unsecured Telnet protocol that may allow a user to create an authenticated session using generic default credentials.CVE-2019-13554 has been assigned to this vulnerability. A CVSS v3 base score of 6.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L). The affected product is shipped with pre-configured hard-coded credentials that may allow root-user access to the controller. A limited application of the affected product may ship without setup and configuration instructions immediately available to the end user. The bulk of controllers go into applications requiring the GE commissioning engineer to change default configurations during the installation process.CVE-2019-13559 has been assigned to this vulnerability.A CVSS v3 base score of 6.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H). | [] | null | null | 6.8 | null |
ICSA-20-105-04 | Siemens Climatix (Update A) | A persistent cross-site scripting (XSS) vulnerability exists in the "Server Config" web interface of the affected devices that could allow an attacker to inject arbitrary JavaScript code. The code could be potentially executed later by another (possibly privileged) user. The security vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires no system privileges. An attacker could use the vulnerability to compromise the confidentiality and integrity of other users' web session. A persistent cross-site scripting (XSS) vulnerability exists in the web server access log page of the affected devices that could allow an attacker to inject arbitrary JavaScript code via specially crafted GET requests. The code could be potentially executed later by another (privileged) user. The security vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires no system privileges. An attacker could use the vulnerability to compromise the confidentiality and integrity of other users' web sessions. | [] | null | 6.1 | null | null |
ICSA-23-348-13 | Siemens SICAM Q100 Devices | The web interface of the affected devices are vulnerable to Cross-Site Request Forgery attacks. By tricking an authenticated victim user to click a malicious link, an attacker could perform arbitrary actions on the device on behalf of the victim user. Affected devices are missing cookie protection flags when using the default settings. An attacker who gains access to a session token can use it to impersonate a legitimate application user. | [] | null | 5.5 | null | null |
ICSA-23-040-01 | Control By Web X-400, X-600M | Control By Web X-400 devices are vulnerable to a cross-site scripting attack, which could result in private and session information being transferred to the attacker.-CVE-2023-23553 has been assigned to this vulnerability. A CVSS v3 base score of 4.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:R/S:U/C:H/I:N/A:N). Control By Web X-600M devices run Lua scripts and are vulnerable to code injection, which could allow an attacker to remotely execute arbitrary code.-CVE-2023-23551 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H). | [] | null | null | 9.1 | null |
ICSMA-19-241-02 | Philips HDI 4000 Ultrasound | The HDI 4000 Ultrasound System is built on an old operating system that is no longer supported. Thus, any unmitigated vulnerability in the old operating system could be exploited to affect this product.CVE-2019-10988 has been assigned to this vulnerability. A CVSS v3 base score of 3.0 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:H/UI:N/S:U/C:L/I:L/A:N). | [] | null | null | 3 | null |
ICSA-22-242-11 | Sensormatic Electronics iSTAR | The affected product is vulnerable to a command injection that could allow an unauthenticated user root access to the system.CVE-2022-21941 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H). | [] | null | null | 10 | null |
ICSA-19-162-04 | Siemens SCALANCE X (Update B) | The affected devices store passwords in a recoverable format. An attacker may extract and recover device passwords from the device configuration. Successful exploitation requires access to a device configuration backup and impacts confidentiality of the stored passwords. | [] | null | 7.1 | null | null |
ICSA-18-018-01A | Siemens SIMATIC WinCC Add-On (Update A) | Malformed ASN1 streams in V2C and similar input files can be used to generate stack-based buffer overflows. The vulnerability could allow arbitrary code execution. CVE-2017-11496 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). Language packs containing malformed filenames could lead to a stack buffer overflow. The vulnerability could allow arbitrary code execution. CVE-2017-11497 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). Zipped language packs with invalid HTML files could lead to NULL pointer access. The vulnerability could cause denial of service of the remote process. CVE-2017-11498 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). A stack overflow flaw in the custom XML-parser could allow remote denial of service. CVE-2017-12818 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). Remote manipulation of the language pack updater could allow NTLM-relay attacks. CVE-2017-12819 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). Arbitrary memory read from controlled memory pointer could allow remote denial of service. CVE-2017-12820 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). A memory corruption flaw could allow remote code execution. CVE-2017-12821 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). The administrative interface can be remotely enabled and disabled without authentication. This could increase the attack surface. CVE-2017-12822 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N). | [] | null | null | 5.3 | null |
ICSA-22-137-01 | Circutor COMPACT DC-S BASIC | A buffer overflow vulnerability has been detected in the firewall function of the device management web portal. The device runs a CGI binary (index.cgi) to offer a management web application. Once authenticated with valid credentials in this web portal, a potential attacker could submit any "Address" value and it would be copied to a second variable with a "strcpy" vulnerable function without checking its length. Because of this, it is possible to send a long address value to overflow the process stack, controlling the function return address.CVE-2022-1669 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:H/PR:L/UI:N/S:U/C:N/I:H/A:H). | [] | null | null | 6.8 | null |
ICSA-19-339-02 | Weidmueller Industrial Ethernet Switches | The authentication mechanism has no brute-force prevention.CVE-2019-16670 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). Remote authenticated users can crash a device by using a special packet.CVE-2019-16671 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H). Sensitive credentials data is transmitted in cleartext.CVE-2019-16672 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). Passwords are stored in cleartext and can be read by anyone with access to the device.CVE-2019-16673 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). Authentication information used in a cookie is predictable and can lead to admin password compromise when captured on the network.CVE-2019-16674 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). | [] | null | null | 9.8 | null |
ICSA-23-278-02 | Qognify NiceVision | Qognify NiceVision versions 3.1 and prior are vulnerable to exposing sensitive information using hard-coded credentials. With these credentials an attacker can retrieve information about the cameras, user information, and modify database records. | [] | null | null | 10 | null |
ICSA-23-257-07 | Rockwell Automation Pavilion8 | The JMX Console within the Pavilion is exposed to application users and does not require authentication. If exploited, a malicious user could retrieve other application users' session data and or log users out of their sessions. | [] | null | null | 8.8 | null |
ICSMA-21-084-01 | Philips Gemini PET/CT Family | The software stores sensitive information in a removable media device that does not have built-in access control.CVE-2021-27456 has been assigned to this vulnerability. A CVSS v3 base score of 2.4 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). | [] | null | null | 2.4 | null |
ICSA-23-201-01 | Schneider Electric EcoStruxure Products, Modicon PLCs, and Programmable Automation Controllers | The affected components contain a vulnerability that could cause arbitrary code execution, a denial-of-service condition, and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. | [] | null | null | 7.5 | null |
ICSA-21-131-01 | Omron CX-One | The affected product is vulnerable to a stack-based buffer overflow, which may allow an attacker to execute arbitrary code.CVE-2021-27413 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). | [] | null | null | 7.8 | null |
ICSA-22-349-19 | Siemens SICAM PAS | Affected software does not properly secure a folder containing library files. This could allow an attacker to place a custom malicious DLL in this folder which is then run with SYSTEM rights when a service is started that requires this DLL.
At the time of assigning the CVE, the affected firmware version of the component has already been superseded by succeeding mainline versions. Affected software does not properly validate the input for a certain parameter in the s7ontcp.dll. This could allow an unauthenticated remote attacker to send messages and create a denial of service condition as the application crashes.
At the time of assigning the CVE, the affected firmware version of the component has already been superseded by succeeding mainline versions. Affected software transmits the database credentials for the inbuilt SQL server in cleartext. In combination with the by default enabled xp_cmdshell feature unauthenticated remote attackers could execute custom OS commands.
At the time of assigning the CVE, the affected firmware version of the component has already been superseded by succeeding mainline versions. | [] | null | 8.3 | null | null |
ICSMA-18-107-01 | Abbott Laboratories Defibrillator | The device 's authentication algorithm, which involves an authentication key and time stamp, can be compromised or bypassed, which may allow a nearby attacker to issue unauthorized commands to the ICD or CRT-D via RF communications.CVE-2017-12712 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H). The ICDs and CRT-Ds do not restrict or limit the number of correctly formatted RF wake-up commands that can be received, which may allow a nearby attacker to repeatedly send commands to reduce device battery life. CVE-2017-12714 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).. Abbott is a U.S.-based company headquartered in Abbott Park, Illinois. Abbott is a U.S.-based company headquartered in Abbott Park, Illinois.. The affected ICDs and CRT-Ds are implantable medical devices designed to deliver high voltage electrical pulses to correct a fast or irregular heartbeat. According to Abbott, these devices are deployed across the healthcare and public health sector. Abbott indicates that these products are used worldwide.CVE-2017-12714 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H). | [] | null | null | 5.3 | null |
ICSA-23-012-06 | Johnson Controls Metasys | Under certain circumstances, the affected versions of Johnson Controls Metasys ADS/ADX/OAS Servers could expose plaintext credentials through application programmable interface (API) calls.-CVE-2021-36204 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). | [] | null | null | 7.8 | null |
ICSA-23-103-13 | Siemens SCALANCE Switch Families | In Wind River VxWorks, memory allocator has a possible overflow in calculating the memory block's size to be allocated by calloc(). As a result, the actual memory allocated is smaller than the buffer size specified by the arguments, leading to memory corruption. An issue was discovered in Wind River VxWorks. The memory allocator has a possible integer overflow in calculating a memory block's size to be allocated by calloc(). As a result, the actual memory allocated is smaller than the buffer size specified by the arguments, leading to memory corruption. | [] | null | 9.8 | null | null |
ICSA-21-229-01 | ThroughTek Kalay P2P SDK | The affected ThroughTek P2P products may be vulnerable to improper access controls. This vulnerability can allow an attacker to access sensitive information (such as camera feeds) or perform remote code execution.CVE-2021-28372 has been assigned to this vulnerability. A CVSS v3 base score 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H). | [] | null | null | 9.6 | null |
ICSA-23-017-02 | Mitsubishi Electric MELSEC iQ-F, iQ-R Series | Mitsubishi Electric MELSEC iQ-F and iQ-R Series products both contain an authentication bypass vulnerability in the WEB server function due to predictable seed in the pseudo-random number generator. CVE-2022-40267 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N). | [] | null | null | 5.9 | null |
ICSA-21-012-04 | Siemens Solid Edge | Affected applications lack proper validation of user-supplied data when parsing PAR files. This could result in an out of bounds write into uninitialized memory. An attacker could leverage this vulnerability to execute code in the context of the current process. Affected applications lack proper validation of user-supplied data when parsing PAR files. This could result in a out of bounds write past the end of an allocated structure. An attacker could leverage this vulnerability to execute code in the context of the current process. Affected applications lack proper validation of user-supplied data when parsing PAR files. This can result in an out of bounds write past the memory location that is a read only image address. An attacker could leverage this vulnerability to execute code in the context of the current process. Affected applications lack proper validation of user-supplied data when parsing PAR files. This could lead to a stack based buffer overflow. An attacker could leverage this vulnerability to execute code in the context of the current process. Affected applications lack proper validation of user-supplied data when parsing DFT files. This could result in an out of bounds write past the end of an allocated structure. An attacker could leverage this vulnerability to execute code in the context of the current process. Affected applications lack proper validation of user-supplied data when parsing of PAR files. This could result in a stack based buffer overflow. An attacker could leverage this vulnerability to execute code in the context of the current process. | [] | null | 7.8 | null | null |
ICSA-22-333-05 | Mitsubishi Electric FA Engineering Software | If this vulnerability is exploited, sensitive information could be disclosed. As a result, unauthorized users can gain access to the CPU module and the OPC UA server module. If this vulnerability is exploited, sensitive information could be disclosed. As a result, unauthorized users could view programs and project files or execute programs. If this vulnerability is exploited, sensitive information could be disclosed. As a result, unauthorized users could view programs and project files or execute programs. If this vulnerability is exploited, unauthorized users could obtain information about the safety CPU module project file. If this vulnerability is exploited, sensitive information could be disclosed. As a result, unauthorized users could access the safety CPU module. If this vulnerability is exploited, sensitive information could be disclosed. As a result, unauthorized users could view programs and project files or execute programs. If this vulnerability is exploited, sensitive information could be disclosed. As a result, unauthorized users could view programs and project files or execute programs. If this vulnerability is exploited, sensitive information could be disclosed. As a result, unauthorized users could view programs and project files or execute programs. If this vulnerability is exploited, sensitive information could be tampered with or disclosed. As a result, information about project files could be obtained without permission by unauthorized users. If this vulnerability is exploited, sensitive information could be disclosed. As a result, unauthorized users could obtain information about the project file for the safety CPU module or the project file for MELSEC Q/FX/L series with security setting. | [] | null | null | 3.7 | null |
ICSA-22-144-01 | Rockwell Automation Logix Controllers | A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.CVE-2022-1797 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:C/C:N/I:N/A:H). | [] | null | null | 6.8 | null |